Chapter 2. Installation
GFK-2571N May 2018 35
2.4 Module Installation
RX3i rack power may be off or on (see Hot
Insertion and Removal for details).
Figure 19: Install Module into RX3i Backplane
Holding the module firmly, align the module
with the correct slot and connector.
Engage the module’s rear pivot hook in the
notch on the top of the backplane (1).
Swing the module down (2) until the module’s
connector engages the backplane’s backplane
connector, and the release lever (PNC001-Ax
only) on the bottom of the module snaps into
place in the bottom module retainer (3).
Visually inspect the module to be sure it is
properly seated.
PNC001-Ax: Tighten the heat sink screw on the
front of the module in the threaded hole in the
back plate to 6 in-lbs (0.68 Nm), using a flat-tip
screwdriver.
PNC001-Bxxx: Secure the bottom of the module
to the backplane using the two captive Phillip’s
head machine screws provided with the module
(not shown in diagram).
2.5 Module Removal
RX3i rack power may be off or on (see Hot
Insertion and Removal for details).
Figure 20: Remove Module from RX3i Backplane
PNC001-Ax: Loosen the heat sink screw on the
front of the module to release the heat sink
from the backplane’s aluminum back plate.
PNC001-Ax: Locate the release lever at the
bottom of the module and firmly press upward
(1), toward the module.
PNC001-Bxxx: Loosen the two captive Phillip’s
head machine screws at the bottom of the
module.
While holding the module firmly and fully
depressing the release lever (PNC001-Ax only),
pivot the module upward until its connector is
out of the backplane (2).
Lift the module up and away from the
backplane to disengage the pivot hook (3).