Chapter 1. Introduction
GFK-2571N May 2018 7
System Maximum Limits
PROFINET Controllers per RX3i CPU
Four PNC001 maximum. Must be located in main CPU rack. Cannot be
located in a remote node.
CPE330 supports one embedded PROFINET Controller plus up to four
PNC001.
CPE400 & CPE100/CPE115 support one embedded PROFINET Controller.
Since these are standalone CPUs they do not support any PNC001 in their
hardware configuration.
IO-Devices per IO-Controller
128 max per PNC001 at maximum update interval.
32 max (simplex) or 20 max (Hot Standby Redundancy) per embedded
PROFINET Controller at maximum update interval.
8 max per RSTi-EP CPE100/CPE115 embedded PROFINET Controller.
For limits at shorter update intervals, refer to PROFINET Controller Loading
Limits in Chapter 3.
Max MRP Clients when configured as MRP
Manager
PNC001 63
Embedded PROFINET Controller - 31
Embedded PROFINET Controller CPE100/CPE115
2
- 8
IO-Devices per Network
Maximum of 255 simplex or 255 redundant I/O Devices per network,
spread across a maximum of 8 I/O Controllers.
The actual total number of devices supported per network depends on the
topology. For details, refer to Maximum Number of Nodes per Network
based on Topology, below.
IO-Devices per RX3i CPU
Maximum of 255 simplex or 255 redundant I/O Devices per RX3i CPU,
spread across up to four PROFINET Controllers.
3
IO-Devices per RSTi-EP CPU
Maximum of 8 simplex I/O Devices for CPE100/CPE115.
IO-Controllers per Network
Eight maximum
Input and output memory per IO-Controller
Maximum of 128 Kbytes combined input and output memory
Note: RSTi-EP CPE100/CPE115 supports maximum 8 IO Devices so the
combined input and output memory is equivalent to maximum input
/output memory supported by 8 devices.
Number of PROFINET Slots per device
256
Number of PROFINET Subslots per slot
256
Number of PROFINET Submodules per RX3i
CPU
2048
Programmer Limits
Number of IO-Controllers
128 (32 RX3i CPU targets × 4 IO-Controllers per RX3i CPU)
Number of IO-Devices
2048 (128 per network × 16 PROFINET networks)
Total number of devices
2176 (does not include backplanes, power supplies, or I/O modules)
For product standards, general operating specifications, and installation requirements, refer to the
PACSystems RX3i System Manual, GFK-2314.
2
Effective with firmware v9.30, CPE100/CPE115 supports MRP.
3
In the case of CPE330, with embedded PROFINET activated, it is possible to have five PROFINET Controllers. However, in
the rare case of having all 5 PNCs configured on the same LAN, and then invoking redundancy, each CPU is again
restricted to a limit of 4 PNCs (in order to satisfy the overall limit of 8 PNCs per LAN).