ADP200 Application PID-IMM User Manual Pag. 71 of 80
5.13 CAN Menu
The parameter in this menu are used only in the ADP200 PID-IMM multi-pump configuration.
The example described in multi pump menu show how program the parameter Slave xActive and master
address.
11602 Slave1Active -
ON - -
11604 Slave2Active -
OFF - -
11606 Slave3Active -
OFF - -
11608 Slave4Active -
OFF - -
11610 Slave5Active -
OFF - -
11612 Slave6Active -
OFF - -
11614 MasterAddress -
3 - -
11616 DivSlaveAddr -
6 - -
11630 MPCopyWDecomp -
OFF - -
12054* COState -
0 - -
12056* SlaveState1 -
OFF - -
12058* SlaveState2 -
OFF - -
12060* SlaveState3 -
OFF - -
12062* SlaveState4 -
OFF - -
12064* SlaveState5 -
OFF - -
12066* SlaveState6 -
OFF - -
Slave1Active If on set the presence of the slave 1. From Default configuration only slave 1 is active.
0=OFF
1=ON
Slave2Active If on set the presence of the slave 2. From Default configuration only slave 1 is active.
0=OFF
1=ON
Slave3Active If on set the presence of the slave 3. From Default configuration only slave 1 is active.
0=OFF
1=ON
Slave4Active If on set the presence of the slave 4. From Default configuration only slave 1 is active.
0=OFF
1=ON
Slave5Active If on set the presence of the slave 5. From Default configuration only slave 1 is active.
0=OFF
1=ON
Slave6Active If on set the presence of the slave 1. From Default configuration only slave 1 is active.
0=OFF
1=ON
MasterAddress
Address of the master drive (Default is 3). Must be equal in all the drives.
Parameter variation have effect only after reset.