ADP200 Application PID-IMM User Manual Pag. 35 of 80
ANALOG INPUTS menu
IPA 1512 Analog Input 1 Top = 32767 cnt IPA 1514 Analog Input 1 Bottom = 0 cnt
IPA 1510 Analog Input Filter = 2 ms IPA 1602 Analog Input 1X Type = 0..10 V
IPA 1612 Analog Input 1X Top = 32767 cnt IPA 1614 Analog Input 1X Bottom = 0 cnt
IPA 1652 Analog Input 2X Type = 0..10 V IPA 1662 Analog Input 2 Top = 32767 cnt
IPA 1664 Analog Input 2 Bottom = 0 cnt
GF-eXpress Diagram:
Figure 19: GF-Express Analog Input 1 Standard
The analog input menu can be changed according the type of pressure sensor used. The application offset
and gain tuning of the analog sensors are required.
For more detail about analog input tuning sequence and parameters see ADP200 FP (Function Parameter)
Manual. Here the most important information. For the pressure sensor analog input (AnInp1Std) offset
command can be done with zero pressure while Gain require the maximum pressure and should be done
only when the machine is running. For the Pressure and Flow (speed) reference, coming from the machine
PLC. Set the two reference to zero value and perform, offset command for the two analog input (AnInp1Exp
and AnInp2Exp). Set the two reference to 100% and perform, gain command for the two analog input
(AnInp1Exp and AnInp2Exp).
Figure 20: GF-Express Analog Input Offset & Gain
4.3.1 Drive Commands
In the factory configuration there are only the following commands: Enable, Start and Fault Reset.
The command may be configured to digital input as shown in the following typical scheme: