38 ADV200 WA • Quick start up guide - Specification and installation
1000 ... 1200 kW
L1 L2 L3 U V W
M
3 ph
L1 L2 L3 U V W
ADV-...-MS..ADV-...-SL
L1 L2 L3 U V W
ADV-...-SL
Output choke
or current-sharing
choke (mandatory)
Output choke
or current-sharing
choke (mandatory)
Output choke
or current-sharing
choke (mandatory)
Note: terminals L1-L2 and L3 are not present in -DC versions.
5.1.9 Braking unit connection (optional)
L1 L2 L3 BR1 BR2 C D U V W
Braking resistor
Note! ADV200 WA-...-4
Terminals BR1/BR2 are standard up to size ADV200 WA-3300, optional in sizes ADV200 WA-4370 ...
5750, larger sizes are not used.
From size ADV200 WA-5900 an optional external BUy braking unit can be used and connected to
terminals C and D. Refer to the BUy handbook for further information.
Recommended combination braking resistors: see paragraph 10.4.
ADV200 WA-...-4-DC
Terminals BR1/BR2 are not present.
An optional BUy braking unit connected to terminals C and D can be used. For further details reference
should be made to the BUy manual.