2 Ingr1!=Ingr2
3 Ingr1<Ingr2
4 Inrg1>Ingr2
5 |Ing1|=|Ing2|
6 |Ing1|!=|Ing2|
7 |Ing1|<|Ing2|
8 |Ing1|>|Ing2|
If set to 0 the comparator is not enabled
If set to 1 the comparator output is enabled when the value of Dig compare input 1 is
inside the window resulting from the value of Dig compare input 2 ± the tolerance set
via the Comparator Window.
If set to 2 the comparator output is enabled when the value of Dig compare input 1 is
not inside the window resulting from the value of Dig compare input 2 ± the tolerance
set via the Comparator Window.
If set to 3 the comparator output is enabled when Compare input 1 is less than Com-
pare input 2.
If set to 4 the comparator output is enabled when Compare input 1 is greater than
Compare input 2.
If set to 5 the comparator output is enabled when the value of Dig compare input 1
is inside the window resulting from the absolute value of Dig compare input 2 ± the
tolerance set via the Comparator Window.
If set to 6 the comparator output is enabled when the absolute value of Dig compare
input 1 is not inside the window resulting from the absolute value of Dig compare
input 2 ± the tolerance set via the Comparator Window.
If set to 7 the comparator output is enabled when the absolute value of Dig compare
input 1 is less than the absolute value of Dig compare input 2.
If set to 8 the comparator output is enabled when the absolute value of Dig compare
input 1 is more than the absolute value of Dig compare input 2.
Menu PAR Description UM Type FB BIT Def Min Max Acc
13.3.6 3672 Compare window perc FLOAT 0.0 0.0 100.0 ERW
Setting of the tolerance window for comparing the Dig compare input 1 and Dig
compare input 2 signals.
Menu PAR Description UM Type FB BIT Def Min Max Acc
13.3.7 3674 Compare delay s FLOAT 0.0 0.0 30.0 ERW
Setting of the delay for signalling the result of the comparison.
Menu PAR Description UM Type FB BIT Def Min Max Acc
13.3.8 3676 Compare output BIT 16 0 0 1 ER
The status of the comparator output is displayed:
0 The result of the set comparison is negative
1 The result of the set comparison is positive