AFE200 • Instruction Manual 115
10 Par 32
If set to 0 the channel is not assigned.
If set to 1 the datum is assigned a 16-bit count.
If set to 2 the datum is assigned a 32-bit count.
If set to 3 16 bits on the channel are reserved for the datum, not used.
If set to 4 32 bits on the channel are reserved for the datum, not used.
If set to 5 the datum is assigned a 16-bit count used by MDPLC.
If set to 6 the datum is assigned a 32-bit count used by MDPLC.
If set to 7 the datum is assigned engineering units on a 16-bit integer.
If set to 8 the datum is assigned engineering units on a 32-bit integer.
If set to 9, the datum is assigned a 16-bit integer engineering unit format not in real
time (5-10ms)
If set to 10 the datum is assigned a 32-bit integer engineering unit format or oat for-
mat if the associated parameter is a oat-type parameter not in real time (5-10ms)
Note! If the sys parameter is not assigned, none of the subsequent fieldbus channels are read, even if
programmed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
14.3.3 4024 Fieldbus M->S1 mon INT32 32 0 0 0 ER
14.3.7 4034 Fieldbus M->S2 mon INT32 32 0 0 0 ER
14.3.11 4044 Fieldbus M->S3 mon INT32 32 0 0 0 ER
14.3.15 4054 Fieldbus M->S4 mon INT32 32 0 0 0 ER
14.3.19 4064 Fieldbus M->S5 mon INT32 32 0 0 0 ER
14.3.23 4074 Fieldbus M->S6 mon INT32 32 0 0 0 ER
14.3.27 4084 Fieldbus M->S7 mon INT32 32 0 0 0 ER
14.3.31 4094 Fieldbus M->S8 mon INT32 32 0 0 0 ER
14.3.35 4104 Fieldbus M->S9 mon INT32 32 0 0 0 ER
14.3.39 4114 Fieldbus M->S10 mon INT32 32 0 0 0 ER
14.3.43 4124 Fieldbus M->S11 mon INT32 32 0 0 0 ER
14.3.47 4134 Fieldbus M->S12 mon INT32 32 0 0 0 ER
14.3.51 4144 Fieldbus M->S13 mon INT32 32 0 0 0 ER
14.3.55 4154 Fieldbus M->S14 mon INT32 32 0 0 0 ER
14.3.59 4164 Fieldbus M->S15 mon INT32 32 0 0 0 ER
14.3.63 4174 Fieldbus M->S16 mon INT32 32 0 0 0 ER
The value received from the bus is displayed. This parameter must be associated with
the src parameter to enable the M->S channel.
The user may modify the M->S and by S->M sys parameters. The consistency of the
sys with the parameter assigned to the channel is checked.
Check for channels M->S:
Sys parameter FB type result
Count 32 32 bit Receives 32 bits from FB and copies to 32 bits of monitor. OK
32_H Receives 32 bits from FB and copies to 32 bits of monitor. OK
32_L Receives 32 bits from FB and copies to 32 bits of monitor. OK
Count 16 16 bit Receives 16 bits from FB and doesn’t know whether to copy to 16H or 16L of
monitor. Error