26 / 66
1436 cPos
12 Parameter table
Configuration
level
Display Function Value range Factory setting
Mode Select operating mode
AUTO
MAN
MAN-FLEX
TEST
OFF
AUTO
1 Service
Submenu for displaying inputs and outputs
I/OStatus
ActiveParaSet
Displays the current active
parameter set
P1 ... P4 P1
min-Pot-max
Displays travel sensor
position in percent
I w
Value of set value signal in
mA
I x*
Value of actual value signal in
mA as a process controller
I Out
Value of actual value output
in mA
W Proc X*
Value of set value signal in
relation to actual value signal
W Pos X
Comparison of set value and
valve position
Pot Abs Travel sensor position
Valve 1:2:3:4
Displays the current position
of the internal pilot valves
Proc Ctrl In*
Deviation between set value
and actual value (process
controller) (%)
Proc Ctrl Out*
Deviation between set value
and actual value (process
controller)
Pos Ctrl In
Deviation between set value
and actual value (positioner)
(%)
Pos Ctrl Out
Deviation between set value
and actual value (positioner)
In w:x:1:2
Displays the current signals
of the digital inputs
Relais K1:K2
Displays the current position
of the internal outputs
Login
Submenu for setting access authorisations
Code Password entry 0...10000 0
Logout Block access OK
New Code: 1 Release the lowest priority 0...10000 0
New Code: 2 Release the medium priority 0...10000 0
New Code: 3 Release the top priority 0...10000 0
Diagnosis
Submenu for displaying diagnostic messages
Error List Displays error messages
hrs Displays operating hours
Warnings
Display warnings during
operation
ON / OFF ON
Errors
Display errors during
operation
ON / OFF ON
SensTest Switch sensor test on or off Disable / Enable1 Disable
Clear Error List Delete error list OK
1436 specific
Submenu for displaying the tool identification
V:1.1.1.1
Displays current software
version
S/N xxx
Displays current serial
number
TAG1 11-digit ID number can be set
TAG2 11-digit ID number can be set
*Only for activated process controllers