General Maintenance
Replacing the glass on a Manual Call Point
a. Disengage the front cover from the call point assembly using the
end of the test key. Insert the key into the slots 'E' and from the
bottom edge lift out the cover.
b. Carefully remove broken glass.
&
Take appropriate precautions when
clearing broken glass to prevent injury.
c. Turn the test key such that the tab is at position 'F' and insert a
new glass as shown.
d. Hook the front cover onto the top edge of the call point assembly
and then push the bottom edge down until it clicks into position.
Check both hooks on the top of the front cover are locked onto
the call point assembly.
e. Turn the test key anticlockwise one quarter of a turn such that the
glass is held under the yellow arm.
S4-34891 Spare MCP glass (Pack of 10)
Resetting the resettable element on a Manual
Call Point
Slide the cover upwards to expose the key hole. Insert the test key in
the keyhole and turn it clockwise by one quarter of a turn. Then turn the
test key anticlockwise by one quarter of a turn to reset the call point
element.
Battery replacement
It is recommended where batteries are installed they must be replaced at 4 Yearly intervals from the date the
system is first commissioned.
"
Any servicing work on the system must be carried out by a suitably trained
person, such as an engineer from the servicing organisation.
26
Operating instructions
E
F
GLASS
YELL