INSTALLATION
 
B
A
3
2
1

 
 
 

 
Thismustbeextended,usingnotlessthan15mmo.d.pipe,
todischarge,inavisibleposition,outsidethebuilding,facing
downwards,preferablyoveradrain.
Thepipemusthaveacontinuousfallandberoutedtoa
positionsothatanydischargeofwater,possiblyboiling,
orsteamcannotcreateanydangertopersons,damageto
propertyorexternalelectricalcomponentsandwiring.
 
a
Condensate produced by the appliance is mildly
acidic (pH 3.5 - 5.0). Use protective gloves
b
Condensate must only be discharged in
accordance with these instructions.
i
The volume of condensates evacuated can reach
about 15 litres per day for a detached house. This
volume is negligible compared to the volume of
waste water discharged by a house, because the
condensates are diluted in this water.
• RefertoBS5546orBS6798foradviceondisposalofboiler
condensate.
1

 
• Makesurethereisnoprotectiveplugtted.
• Connectthecondensatepipe(1).
i
The pipe should have a fall of a least 2.5° 44mm/
metre away from the boiler.
Condensateshould,ifpossiblebedischargedintothe
householdinternaldrainagesystem.
• Ifthisisnotpracticable,dischargecanbeallowedintothe
externalhouseholddrainsorapurposedesignedsoakaway,
refertodiagramoverleaf.
Itisrecommendedthatanyexternalcondensatedrainpipeis
protectedandalsopreferablyof32mmdiameter,toprevent
freezinginadverseweatherconditions.
• Alwaysensurethepipeisinstalledwiththecorrectfall
• Connecttheboilercondensatedrain(1)toacondensate
dischargepipewhichshouldbeminimumof19mm
internaldiameterandbemadeofanacidresistantmaterial
(e.g.plasticoverowpipe).Donotusemetalpipes.Itis
permissibletouseacondensateneutraliserprovidingthatit
ischeckedforcorrectoperation.