- 18 -
INSTALLATION
 
 

a
If necessary, you must install a terminal
protection kit.
Ø 60/100 mm
L
63
1


Ø 80/125 mm
L
1







Ø60/100 10m
Ø80/125 20m 25m
Eachtimeanadditional90°bendisnecessary(or2at45°),the
length(L)mustbereducedby1m.
 

L





Ø60/100 10m
Ø80/125 20m 25m
Eachtimeanadditional90°bendisnecessary(or2at45°),the
length(L)mustbereducedby1m.
 

b
The ue connecting from the appliance to
the ue system must be supplied from the
manufacturer of the boiler.
b
C43 ue systems must not be a 'pressurised
system' but act under natural draught principles
b
C43 type ue systems must have their
own condensate drain tted and not allow
condensate to mix into other appliances