INSTALLATION
Theaccesstotheboilerstechnicaldataallowsyoutoadjustthe
boilertotheexactsystemrequirements.
Note:theheatingpowerdecreasehasnoeffectonthedomestic
hotwaterpower.
• Pressformorethan7secondsonthebutton to
accessthecongurationmenu.Thescreendisplays"0".
• Press4timesonthebutton
underthesymbol .
Thescreendisplays"96".Thisistheinstaller'spassword.
• Presson
tovalidate.Thescreendisplaysthe
parameter"00"anditsvalue"XX”.
• Pressonbutton
or underthesymbol toaccessthe
parametertomodify.
• Pressonbutton
or underthesymbol tomodifythe
valueoftheparameter.
• Dolikewiseforeachparameterthatneedstobemodied.
• Pressformorethan3secondsonthebutton
toexit
thecongurationmenu.
d.00 Maximumheatingpower kW
Chooseavalue:
12sxi4to12kW
18sxi5to18kW
30sxi8to30kW
12
18
30
yes
d.01 Pumpover-runtime-heating min. Chooseavaluebetween2and60. 5 yes
d.02
Blockingtimeforburnerinheating
mode(anti-cycletime)
min.
Topreventtheburnerfrequentlyswitchingonandoff,
thereactivationoftheburneriselectronicallyblockedforaperiod
thatisdeterminedeachtimetheburnerstops.Theburnerblocking
timecanbeadaptedtotheusageconditionsfortheheating
installationanddependsonthetemperaturethatissetforheating:
-at80°C,theperiodisxed(2minutes)
-at10°C,theperiodisadjustable:chooseavaluebetween2and
60minutes.
20 yes
The following menu is displayed if a domestic hot water tank is connected to the appliance.
d.03 TemperatureoftheDHWoutlet °C DisplaythetemperatureoftheDHWoutlet. - no
d.04 Temperatureofwaterinthetank °C Displaytankwatertemperature. - no
d.18 Pumpfunction -
Mode:
0=Withtheburner
1=Continuouswithambienttemperature
2=Continuous
1 yes
d.19 Speedofthepump -
Functioningmode:
0=Automatic:maximumspeedwhentheburnerisswitchedon
1=Minimumspeed
2=Automatic:automaticspeedwhentheburnerisswitchedon
3=Maximumspeed
2 yes
d.20
Maximumtemperaturesettingfor
domestichotwater
°C
Therecommendedmaximumtemperaturesettingfordomestichot
wateris60°C.Chooseavaluesuitableforyourneeds.
60 yes
The following 2 menus are displayed if an option card (not supplied) is installed on the appliance.
d.27 Functionrelay1 - Reservedforfutureuse 1 yes
d.28 Functionrelay2 - Reservedforfutureuse 2 yes