- 16 -
INSTALLATION
 
 
b
Only ue accessories supplied by Glow-worm
must be used.
Differentueoutletcongurationscanbecarriedout.
• Consultyoursupplierformoreinformationabouttheother
possibilitiesandassociatedaccessories.
44 mm/m
1 2
4 3
• Standardueterminalkitshaveanin-builtfallbacktothe
boilertodrainthecondensate.Thesecanbettedlevel
betweentheapplianceandtheterminationposition.Allother
extendeduesmusthaveafallofatleast44mm/m
Themaximumlengthoftheueoutletisdenedaccordingtoits
type(forexampleC13).
• Whateverthekindofuesystemchosen,observethe
minimumdistancesindicatedinthechartbelowtoposition
theueterminals.
• Toinstalltheue,refertotheseparateueinstruction
suppliedwithyourappliance.
• Explaintheserequirementstotheuseroftheappliance.
a
If necessary, you must install a terminal
protection kit.
b
Caution! The connection between the ue elbow
and the ue outlet must be sealed.
theminimumacceptablesitingdimensionsforthe
terminalfromobstructions,otherterminalsandventilation
openingsareshownindiagramoverleaf.
theminimumdistancesforueterminalpositioningmust
bethosedetailedinI.S.813“DomesticGasInstallations”.
Theterminalmustbeexposedtotheexternalair,allowingfree
passageofairacrossitatalltimes.
Beingacondensingboilersomeplumingmayoccurfrom
theueoutlet.Thisshouldbetakenintoconsiderationwhen
selectingthepositionfortheterminal.
Carportsorsimilarextensionsofaroofonly,oraroofandone
wall,requirespecialconsiderationwithrespecttoanyopenings,
doors,ventsorwindowsundertheroof.Careisrequired
toprotecttheroofifmadeofplasticsheeting.Ifthecarport
comprisesofaroofandtwoormorewalls,seekadvicebefore
installingtheboiler.
b
If the ue terminal is positioned near a light
source insects may enter the ue system.
Where safe and practical to do so advise the
homeowner to check the ue outlet and clear
visible insects from the terminal end.