MAINTENANCE
F26 Faultingasvalvemotor. Disconnectedordefectivecables
•Checkthegasvalveconnections.
•Checktheoperationofthegasvalve.
•Checktheoperationofthecondensatepump(option).
F27 Flamedetectionfault. Abnormalamedetection
•Checktheamedetectionelectrode.
•Checkthemainboard.
•Checktheigniterunit.
F28 Ignitionfault
Noreturngas/Insufcientgasow
Gasvalveincorrectlyadjusted
Defectiveringelectrodeandame
control/Defectiveigniterunit
•Checkthereturngascircuit(gasvalveopen).
•Checktheobservetheamepictureandcheck
theCO
2
setting.
•Checktheigniterunitconnections.
•Checkthestateoftheelectrode(corrosion).
F29 Lossofameduringoperation
F32 Incorrectairpressure Incorrectfanspeed.
•Checktheentireuesystem.
•Checkthefan’selectricalconnections.
F49 EBUSvoltagefault
FaultinEBUSline
ShortcircuitinEBUSconnector
•CheckthattheeBuscontrolsarettedandwired
correctly.
F61
Faultinthemainboard
Gasvalvecommandfault
•Checkthemainboardsconnections.
•Checkthemainboard.
•ChecktheapplianceDSNnumberiscorrect.
•Resettheappliance.
F62 Gasvalveclosurefault
F63 Faultinthemainboardmemory
F64
Rapiductuationofreturnorow
heatingsensor.
F65 Excessivemainboardtemperature
F67 Flamesignalfaultinthemainboard
F68 Fluctuationofamesignal
Noreturngas/Insufcientgasow
Gasvalveincorrectlyadjusted
Defectiveringelectrodeandame
control/Defectiveigniterunit
•Checkthereturngascircuit(gasvalveopen).
•Checktheobservetheamepictureandcheck
theCO
2
setting.
•Checktheigniterunitconnections.
•Checkthestateoftheelectrode(corrosion).
F70
Userinterfaceincompatiblewiththemain
board
Incorrectproductcode
•CheckthattheapplianceDSNcodeonthescreen
matchestheproductcodeofthenameplate(inthe
eventofafaultandtheapplianceDSNdoesnot
appear,consultmenu.d.93reservedforthecode).
•Checktheboardsreference.
F71 Flowheatingtemperaturesensorfault
Flowheatingtemperaturesensor
unclippedordefective(no
temperaturevariation)
•Checkthesensorconnections.
•Makesurethatthesensorisclippedtothetube.
F72
Permanenttemperaturedifferencebetween
owandreturnheatingsensors
Mismatchbetweentheowandreturn
heatingtemperatures(permanent
difference)
•Checktemperaturesensorsconnections.
•Replacefaultysensors.
F73 Heatingcircuitpressuresensorfault Thesensorisshortedordisconnected.
•Checkthesensor’sconnections.
•Checkthesensor.
F74 Heatingcircuitpressuresensorfault Faultinpressuresensor
F76 Thermalfusefault
Thermalfusedisconnected
Defectivethermalfuse
•Checkthefusesconnections.
•Replacetheheatexchanger.
F77 Faultingasvalvemotor.
Defectivegasvalve.
Defectivecondensatepump(option)
•Checkthegasvalveconnections.
•Checktheoperationofthegasvalve.
•Checktheoperationofthecondensatepump(option).
F83
Nowaterintheinstallation:thetemperature
doesnotincreasewhentheburnerislit
Returnwatervalveclosed
Pumpdisconnected
Leakintheinstallation
•Filltheinstallation.
•Purgetheinstallation.
•Checkthepumpconnections.
•Checktheowandreturnheatingsensor
connections.
•Checkthattherearenoleaks.
F84
Permanenttemperaturedifferencebetween
owandreturnheatingsensors
Invertedordisconnectedowand
returnheatingtemperaturesensors
Defectivetemperaturesensors
•Checktemperaturesensorsconnections.
•Replacefaultysensors.
F85 Flowandreturnheatingsensorsfault
Flowandreturnheatingtemperature
sensorconnectedtosametube
•Checktemperaturesensorsconnections.
F86 Underoorheatingcontactfault
Floorheatingcontactopen
Sensordisconnectedordefective
•Checkthesensorconnections.
•Checkthatthesensorisconnectedtothemain
boardandtheshuntisremoved.
Err Userinterfacefault Defectiveuserinterface
•CheckconnectionfromuserinterfacePCBtomain
PCB.
•Replaceuserinterface.