8.7.13 Pump cascade control (4.2)
Fig. 52 Pump cascade control
In the menu, you can set the functions connected to pump
cascade control.
The following menus can be selected:
Min. time between start/stop
Max. number of starts/hour
Standby pumps
Forced pump changeover
Pump test run
Pilot pump
Pump stop attempt
Pump start and stop speed
Min. performance
Compensation for pump start-up time.
8.7.14 Min. time between start/stop (4.2.1)
Fig. 53 Min. time between start/stop
Description
The function ensures a delay between the starting and stopping
of one pump and the starting and stopping of another pump.
The purpose is to prevent hunting when pumps start and stop
continuously.
Setting range
From 1 to 3600 seconds.
Setting via the operating panel
Settings > Pump cascade control > Min. time between start/stop.
Factory setting
The setting is done in the startup wizard and depends on the
application.
8.7.15 Max. number of starts/hour (4.2.1)
Fig. 54 Max. number of starts/hour
Description
The function limits the number of pump starts and stops per hour
for the complete system. It reduces noise emission and improves
the comfort of systems with mains-operated pumps.
Each time a pump starts or stops, CU 352 calculates when the
next pump is allowed to start/stop in order not to exceed the
permissible number of starts per hour.
The function always allows pumps to be started to meet the
requirement, but pump stops will be delayed, if needed, in order
not to exceed the permissible number of starts per hour.
The time between pump starts must be between the minimum
time between start and stop, see section 8.7.14 Min. time
between start/stop (4.2.1), and 3600/n, n being the set number of
starts per hour.
Setting range
1 to 1000 starts per hour.
Setting via the operating panel
Settings > Pump cascade control > Max. number of starts/
hour.
1. Set:
Min. time between start/stop.
Max. number of starts/hour.
Factory setting
MPC-E: 200 starts per hour
Other variants: 100 starts per hour.
This function has no influence on 8.7.24 Stop
function (4.3.1).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos Control MPC 2000 Series and is the answer not in the manual?

Grundfos Control MPC 2000 Series Specifications

General IconGeneral
BrandGrundfos
ModelControl MPC 2000 Series
CategoryControl Systems
LanguageEnglish

Related product manuals