8.7.68 Fault, feedback sensor (4.4.10)
Fig. 120 Fault, feedback sensor
Description
You can set how the system is to react if the primary sensor fails.
Setting range
Stop (without delay)
Stop (with delay)
•Min.
•Max.
User-defined
Operating mode "Local"
Emergency run
Reset: Manual or Auto.
Setting via the operating panel
Settings > Monitoring functions > Fault, feedback sensor.
1. Select reaction in case of a fault in the primary sensor.
2. Select resetting: Manual or Auto.
8.7.69 Non-return valve (4.4.11)
Fig. 121 Non-return valve
Description
The function enables CU 352 to detect if a "Non-return valve" is
leaking or faulty. A small leakage will after five accumulated
incidents result in a warning. A faulty NRV will instantly result in
an alarm and pump stop. In this case the motor is not able to
overcome the backflow through the pump with the faulty NRV.
Setting range
Monitoring, non-return valve: Enabled or Disabled.
Automatic resetting of alarm: Enabled or Disabled.
Setting via the operating panel
Settings > Monitoring functions > Non-return valve
1. Enable the function.
2. Select if "Automatic resetting of alarm" is to be "Disabled".
Factory setting
The function is "Enabled".
The function is only valid for a MPC-E system with
MGE motors model G, H, I or J.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos Control MPC 2000 Series and is the answer not in the manual?

Grundfos Control MPC 2000 Series Specifications

General IconGeneral
BrandGrundfos
ModelControl MPC 2000 Series
CategoryControl Systems
LanguageEnglish

Related product manuals