5. Installation requirements
5.1 Installing the product in areas with high humidity
WARNING
Fire hazard
Death or serious personal injury
‐ In high humidity environments where condensation
can occur, connect the product permanently to the
power supply and activate the standstill heating
function.
To maintain the cURus mark, additional requirements
apply to the equipment. See the appendix concerning
installation in the USA and Canada.
Do not expose the product to UV radiation.
To avoid condensation, the drive must be continuously
energized due to the application of heat, with interruptions
such that cooling to the point of condensation does not
occur.
• Open the drain holes in the product.
When you open the drain hole, the enclosure class of
the motor will be lower than standard.
• Connect the product permanently to the power supply. In areas
with a high humidity, activate the built-in standstill heating
function.
Related information
6.1.1.2 Drain holes
5.2 Location
Observe the instructions on intended use for your specific product
regarding indoor and outdoor location.
Related information
2.1 Related instructions
5.3 Minimum space
5.3.1 Cooling the motor
• Install the motor allowing a distance of minimum 2 inches (50
mm) (D) between the end of the fan cover and the wall or
another fixed object.
TM082853
Model K
• Position the product with sufficient space around.
• Make sure that the temperature of the cooling air does not
exceed 122 °F (50 °C).
• Keep cooling fins and fan blades clean.