The sensors must have the same unit and must
be set as feedback sensors. You can set the
sensors manually, sensor by sensor, or by using
the Assist menu. See the section on assisted
pump setup.
p
p
p
TM057888
p
p
p
TM057889
Controller settings
For recommended controller settings, see the section
on the controller.
Related information
9.16 Controller (Controller settings)
9.51 Assisted pump setup
9.5.5 Constant differential temperature
The pump maintains a constant differential
temperature in the system and the pump performance
is controlled according to this.
H
Q
t
TM057954
Constant differential temperature
This control mode requires either two temperature
sensors or one external differential-temperature
sensor. See the examples below.
The temperature sensors can either be analog
sensors connected to two of the analog inputs or two
Pt100/1000 sensors connected to the Pt100/1000
inputs, if these are available on the specific pump.
Set the sensor in the Assist menu under Assisted
pump setup. See the section on assisted pump
setup.
Examples:
t
t
Δt
TM057891
Two external temperature sensors.
Constant differential-temperature control is
achievable with two temperature sensors. The
pump uses the inputs from the two sensors and
calculates the differential temperature.
The sensors must have the same unit and must
be set as feedback sensors. You can set the
sensors manually, sensor by sensor, or by using
the Assist menu. See the section on assisted
pump setup.
t
t
t
TM057894
One external differential-temperature sensor.
The pump uses the input from the sensor to
control the differential temperature.
You can set the sensor manually or by using the
Assist menu. See the section on assisted pump
setup.
t
TM057931
Controller settings
For recommended controller settings, see the section
on the controller.
Related information
9.16 Controller (Controller settings)
9.51 Assisted pump setup
9.5.6
Constant flow rate
The pump maintains a constant flow in the system,
independently of the head.
52
English (GB)

Table of Contents