Alarm management
7.8 System alarms
For the meanings of the dierent critical system alarms, refer to the table
below:
Error code Severity Meaning Recommended action
E001 High L1 current sensor damaged Contact your Hager
representative or local Hager
technical support (contact
details on the Hager website
for your country).
E002 High L2 current sensor damaged
E003 High L3 current sensor damaged
E004 High N current sensor damaged
E005 High MHT actuator damaged
E006 High Critical error 4: faulty hardware
board
E007 High Critical error 3: faulty hardware
board
E008 High Critical error 2: corrupted memory
E009 High Rating plug damaged Replace the rating plug.
E010 High Critical error 5: software error Contact your Hager
representative or local Hager
technical support (contact
details on the Hager website
for your country).
E011 High Critical error 1: faulty hardware
board
E012 High Trip unit overheat Check that the temperature
inside the electrical
distribution board is not
abnormal.
Step/Action Button Display
1 When the HWF alarm is
set to alarm, the following
ashing message pop-up
appears.
2 Briey press the trip unit's
OK button to hold the pop-
up and display the system
alarm code generated by
the malfunction.
E003
12/12/2022 - 18:24:05
HWF
3 Do a long press on the
OK button for more than 3
seconds to acknowledge
and close the message
after having resolved the
trip fault.
Case of HWF alarm set to "Alarm"