148 6LE008146B
Event management
List of events in Alarm and Optional alarm sections
No. Text Section Type Unlock Severity Indicated
on the
display
12 PTA1 overload pre-alarm Alarm Instantaneous Autoreset Average Yes
13 PTA2 overload pre-alarm Alarm Instantaneous Autoreset Average Yes
24 Overload alarm Alarm Instantaneous Autoreset High Yes
1 Undervoltage protection alarm Alarm Appearance/end Manual High Yes
2 Overvoltage protection alarm Alarm Appearance/end Manual High Yes
3 Underfrequency protection alarm Alarm Appearance/end Manual High Yes
4 Overfrequency protection alarm Alarm Appearance/end Manual High Yes
5 Reverse active power protection alarm Alarm Appearance/end Manual High Yes
6 Current unbalance protection alarm Alarm Appearance/end Manual High Yes
7 Voltage unbalance protection alarm Alarm Appearance/end Manual High Yes
26 Voltage dip alarm Alarm Appearance/end Manual Average Yes
27 Voltage swell alarm Alarm Appearance/end Manual Average Yes
9 Electronic trip unit HWF failure alarm Alarm Appearance/end Manual High Yes
21 Grouped alarm Alarm Appearance/end Autoreset Average No
23 Low or missing battery alarm Alarm Appearance/end Autoreset Average Yes
25 Maintenance alarm Alarm Appearance/end Manual Average Yes
- Optional alarm (1 to 12) Custom alarm Appearance/end Manual Average Yes