150 6LE008146B
Event management
List of events in the Diagnostic section
List of events in the Operation section
No. Text Section Type Unlock Severity Indicated
on the
display
1 Bluetooth communication error Diagnostic Instantaneous Autoreset Low No
10 Date and time reset Diagnostic Instantaneous Autoreset Low No
9 Trip unit powered by USB-C Diagnostic Appearance/end Autoreset Low No
8 Trip unit powered by external 24V power
supply
Diagnostic Appearance/end Autoreset Low No
7 No backup battery detected Diagnostic Appearance/end Autoreset Low No
6 History section(s) erased Alarm Instantaneous Manual High No
4 Connection to Bluetooth port Diagnostic Instantaneous Autoreset Low No
3 Bluetooth communication established Diagnostic Instantaneous Autoreset Low No
2 Connection to USB port Diagnostic Instantaneous Autoreset Low No
13 Loss of communication with the OAC alarm
output contacts module
Diagnostic Appearance/end Autoreset Low No
No. Text Section Type Unlock Severity Indicated
on the
display
59 HWF protection operation Operation Instantaneous Autoreset Low No
57 HWF protection start Operation Instantaneous Autoreset Low No
58 HWF protection end Operation Instantaneous Autoreset Low No
62 Swell detection start Operation Instantaneous Autoreset Low No
63 Swell detection end Operation Instantaneous Autoreset Low No
60 Dip detection start Operation Instantaneous Autoreset Low No
61 Dip detection end Operation Instantaneous Autoreset Low No
45 Circuit breaker in Test position Operation Instantaneous Autoreset Low No
44 Circuit breaker in Connected position Operation Instantaneous Autoreset Low No
43 ZSI output contact GF closed Operation Appearance/end Autoreset Low No
42 ZSI output contact STD closed Operation Appearance/end Autoreset Low No
41 ZSI input GF activated Operation Appearance/end Autoreset Low No
40 ZSI input STD activated Operation Appearance/end Autoreset Low No
38 Circuit breaker closed by remote control Operation Instantaneous Autoreset Low No
37 Circuit breaker opened by remote control Operation Instantaneous Autoreset Low No
32 OAC DO1 contact closed Operation Appearance/end Autoreset Low No
33 OAC DO2 contact closed Operation Appearance/end Autoreset Low No
34 OAC DO3 contact closed Operation Appearance/end Autoreset Low No
35 OAC DO4 contact closed Operation Appearance/end Autoreset Low No
36 OAC DO5 contact closed Operation Appearance/end Autoreset Low No
31 Trip unit acknowledgement Operation Instantaneous Autoreset Low No
30 Circuit breaker closed Operation Instantaneous Autoreset Low No
29 Air circuit breaker Operation Instantaneous Autoreset Low No
28 Advanced protections inhibition command Operation Appearance/end Autoreset Low No
27 Operation on profile B Operation Appearance/end Autoreset Low No
26 Forced electromechanical tripping Operation Instantaneous Autoreset Low No
20 Reverse active power protection operation Operation Instantaneous Autoreset Low No