HDL KNX / EIB Switch Actuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL)
www.hdlchina.com 30/58
---Threshold 1 value is (0...255)
Set threshold 1 value between 0 and 255. Default is 80
Options:0..255
---Threshold 2 value is (0...255)
Set threshold 2 value between 0 and 255.Default is 180
Options:0..255
---“Threhold input(0..255)” after bus voltage recovery
The default input threshold value is set after power on recovery
Options:0..255
---{Input object value<lower threshold}
If the value of receiving telegram from bus lower than the minimum
threshold value, the switch will action according to below option ( ON
or OFF or no action)
Options: Unchange
ON
OFF
Unchange: The channel switch position no change
ON: The channel switch position set to ON.
OFF: The channel switch position set to OFF
.
---{Lower threshold<=Object vlue<=Upper threshold}
If the value of receiving telegram from bus between Lower
threshold and Upper threshold, the switch will action according to
below option ( ON or OFF or no action)
Options: Unchange
ON
OFF
Unchange: The channel switch position no change.
ON: The channel switch position set to ON.
OFF: The channel switch position set to OFF
---{Input object value>upper threshold}