HDL KNX / EIB Switch Actuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL)
www.hdlchina.com 47/58
4.2.11 Objects “Threshold”
NO. Object name Function Flags Data type
21
Output N Threshold input C W U EIS14
DPT 5.004 1byte
EIS10
DPT 7.001 2bytes
If this communication object is actived , the threshold input value from bus compare with
threshold 1 and threshold 2, and calculate the status of switch according to the setting of
database.
22
Output N Change threshold
1
C W U EIS14
DPT 5.004 1byte
EIS10
DPT 7.001 2bytes
Change threshold1 value via bus.
23
Output N Change threshold
2
C W U EIS14
DPT 5.004 1byte
EIS10
DPT 7.001 2bytes
Change threshold2 value via bus.
Table 15 Threshold
4.2.12 Objects “Blinds”
NO. Object name Function Flags Data type
24
Output N Moving for
Blinds(0-UP,1-DOWN)
C W U EIS1
DPT 1.008
1bit
This communication object control blinds move UP/DOWN. The blinds move UP/DOWN
run or stop by the value of receiving telegram from the bus or stop until timeout .
25
Output N Adjust/Stop for Blinds C W U EIS1
DPT 1.007
1bit
This communication object control blinds adjust or stop. If the blinds moving,Then
receiving ‘1’ or ‘0’ for stop moving.Otherwise adjust the blinds.
Table 16 Blinds