24
13 Event record
The meter is able to record a large quantity of events, which comprise many different types of
events. The event type, corresponding record format, event code, judge method and record
capacity could be seen in the later description
13.1 Standard event
No special characteristics are declared in this kind of events.
Record format: event code and occurring time.
Up to 100 entries of standard events can be recorded.
Tab 13.1.1 Standard event
Code Corresponding event Judgment
3 Switch to DST The meter switches to DST automatically and
the time before switch is recorded.
Clock adjusted(old date/time)
Clock is modified through by command
Clock adjusted(new date/time)
Clock is modified through by command
6 Clock failure(RTC error) Format of clock incorrect
8 Low Battery Voltage The battery voltage is lower than 3V
10 Error register cleared The Error register is cleared
The alarm register is cleared
The Measuring unit is fault
Firmware ready for activation
Confirmation of firmware upgrade
18 Firmware activated Firmware upgrade has finished
19 Firmware failure Firmware is failure
29 Billing Billing
30 Program parameters Program parameters
Charge(only for prepaid mode)
Charge, only for prepaid mode
Passive tariff table activate
36 Prepayment management Prepayment management
Modified CT or PT ratio, only for CT PT type
modified the TOU parameters
44 Load Profile Reset Reset the Load Profile
49 Key update The Key is update
55 EEPROM hardware error start EEPROM hardware is error
57 Data flash hardware error start Data flash hardware is error