VC3000Pro Series Vision Controller User Manual
31
Solution
Check if the signal source has any edge signal trigger; check if the parameters are correctly
configured (for example, filter parameter, mode configuration delay).
If the electrical output level does not change, check if the wirings are correct (C port and G port
need external power supply) and check if the parameter settings are completely enabled.
Replace the device and check if the IO port is burned out.
8.4 Why VC3000Pro Controller can run extended modules, but
setting parameters failed?
Problem
Mismatch between the serial port No. and the DIP switch No. that is set as ON.
Solution
Check if there is correct corresponding relation between the serial port No. and the DIP switch
No. that is set as ON. The serial port No. ranges from COM 11 to COM 12, and the corresponding
DIP switch No. is from 5 to 6.
If there are multiple extended modules, make sure that each module only has one DIP switch No.
that is set as ON, and does not conflict with other module’s DIP switch settings.