HOIST OVER-WEIGHT FUNCTION
The VFD is setup to use the output current to the motor as the over-weight function. The VFD uses (2) over-weight current
parameters. Over---weight (2) is when operating
above low--weight (1) and over-
Having (2) over-weights greatly increases over-weight accuracy and decreases the likelihood of a false over-weight condition.
The VFD has an alternative over-weight current parameter source that can be configured. This is normally used in applications where
the hoist over-weight needs to be limited to a lower value in certain parts of a building or runway. The alternative over-weight uses (2)
over-weight current parameters in the same configuration as the standard over-weight function. To use the alternative over-weight,
configure the parameters in the chart below and modify the over-weight circuit to switch the source of the signal to the 24v DPDT
relay between digital output 11 and digital output 14.
The VFD has (3) configurations for the over-weight signal, external momentary, external maintained, Internal.
External momentary - will output a signal when the condition is met but will not maintain the output after the condition is no longer
met.
External maintained - will output a signal when the condition is met and maintain the signal until the reset condition is met or power is
cycled.
Internal - s to function. Internal works the same way as the external maintained but will internally
prevent the hoist up function until the reset condition is met or power is cycled.
NOTE
Internal is only latched to the STANDARD OVER-WEIGHT function.
HOW IT WORKSWhen the output current to the motor exceeds the value in the conditional over-weight current parameter for an
amount of time that exceeds the detection delay time, the conditional digital output will turn on and activate a 24v relay to interrupt
the hoist E-Stop circuit. The signal is turn off once the hoist has lowered for 2.0 seconds.
HOIST OVER-WEIGHT PARAMETERS
Function
Parameters
Example Value
Over-Weight Signal Output Type
UE-54
0 = External Momentary
1 = External Maintained
2 = Internal
Over-Weight Detection Delay Time
UE-55 150 = (1.5 seconds)
Over-Weight Reset Time
UE-56 200 = (2.0 seconds)
Standard Over-Weight
Standard Over-Weight (1) Value *Low Speed
CE106 14.0 Amps
Standard Over-Weight (2) Value *High Speed
CE107 15.0 Amps
Digital Output 11 Function
CC-01 69:MO1
Digital Output 11 Status
CC-11 00: N.O
Alternative Over-Weight
Alternative Over-Weight (1) Value *Low Speed
CE102 10.0 Amps
Alternative Over-Weight (2) Value *High Speed
CE103 11.0 Amps
Digital Output 14 Function
CC-04 73:MO5
Digital Output 14 Status
CC-14 00: N.O