TROUBLESHOOTING E51 FAULT
WHAT IS AN E51 FAULT - An E51 fault . The motor responded with less than the anticipated motor
current.
HOW IS AN E51 FAULT DETERMINED When the VFD is operating in closed loop vector control only (AA121 = 10) at the start of a lift
cycle -32 for the motor to respond
with the motor current. If the motor responds with less than the anticipated output currencurrent
calculation, determined to have occurred.
If this fault is occurring at random it might be caused due to a high load or overload. If a high load or overload occurs it can
mes set a value in which the VFD & motor would need to prove a value higher than allowed. Check to make sure the
motor brake circuit is not dropping out randomly. Check to see if the encoder signal in unstable by using dA-08 detected
speed monitor, this value while run should be close to the set--08 is + / -

 and make sure the VFD is not driving through the motor
-


in the brake spec.

Check to see if the motor Io constant Hb116 was changed to a larger value than what’s on the motor nameplate. Please not

Make sure all loads are removed from the hook block and switch the VFD to an open loop control mode and see if the hoist
works properly and the output current isn’t high and running smoothly. This will help determine if an IGBT output from the
VFD is bad.
Check parameter UE-68 and UE-69 should have a value of 1500 2000.
Check parameter UE-32 should have a value around 250 400.
Check parameter bA103 = 0.00 and bA101 = 00: Disabled.
Check parameter bA110 = 07: Keypad.
Contact Detroit Hoist for further assistance.