Page 50
FAULT / ERROR CODES DESCRIPTION
Fault / Error Code
Description
E001
Over-current error
E005 / E039
Electronic thermal overload error (motor current > bC110)
E006
Dynamic braking resistor over used error
E007
DC-Bus over-voltage error
E008 / E011
Memory error / CPU error
E009
Undervoltage error
E010
Built-in current detector error
E012
External trip error (digital input configured for Ext)
E013
USP error
This error occurs if an operation command has been input to the inverter when the power supply is
turned ON. Operation command detection is carried out for 1 second after the power supply is turned
ON. (When USP function is selected.)
E014
Ground fault error
E015
Incoming voltage error (input power supply is too high)
E016
Instantaneous power failure error
E019
Temperature detector error
E020
Temperature error Cooling fan rotation speed reduction error
E021
Temperature error
E024
Input open-phase error
When [bb-65] input phase loss selection is set to 01, and when a missing phase is detected in input line,
the inverter turns OFF its output.
E030
IGBT error (ground fault to motor or on output of VFD)
E034
Output open-phase error
When the output phase loss selection [bb-66] is set to 01, when a loose connection or disconnection of
output line, disconnection inside the motor, etc. is detected, the inverter turns OFF its output.
Detection of phase loss state is executed in the section between 5Hz to 100Hz.
E035
Thermistor error
E036
Brake error
E038
Low-speed range overload error
E039
Electronic thermal overload error (motor current > bC110)
E040
Operator keypad communication error
E041
RS485 / EZCOM communication error When CF-05 = 0 or 1
E042
RTC error
E043 / E044 / E045
Internal Program illegal instruction error