CONFIGURING AN OUTUT FOR FAULT SIGNAL
The VFD will come from Detroit Hoist with output 16 (dry contact) already configured for fault alarm signal. If you need to switch the
fault alarm signal to a different output, use the chart below.
CC-01 thru CC-05 (24vdc digital i/o)
017 = AL (Alarm)
CC-06 (16 relay dry contact)
RESET FAULT USING INPUT
Resetting a fault remotely using an input to the VFD can be done by configuring one of the available digital inputs for reset. Use the
chart below.
CA-04, CA-06
028 = RS
CA-08, CA-09
(when using encoder limits with parameters UE-33 = 2)
OUTPUT 0-10V / 4-20mA
The output analog can be configured for multiple functions. Listed below are the most common functions used for hoist and crane
applications. If the function is not present, please contact Detroit Hoist for further assistance.
Ao1 – Analog output 1 function
Cd-04
dA-02 = Output Current
Ao2 – Analog output 2 function
Cd-05
Analog monitor adjust mode
Cd-10
1 = Outputs to terminals output levels in the
adjustment mode.
Filters and outputs the selected data.
Cd-22
Outputs the absolute value of data
Outputs data with a symbol as is.
Ao1 monitor bias adjustment
Biases data to adjust Point 0 of data.
Ao1 monitor gain adjustment
Cd-24 -1000.0 –
Apply a gain to data to adjust an inclination in
data.
Ao1 output level setting at Ao1
monitor adjust mode
Cd-25 -100.0 –
Sets output in the adjustment mode. It selects
-22]=00), or the
minimum output (at --22]=01).
Filters and outputs the selected data.
Cd-32
00 = Absolute data
01 = Signed data
Outputs the absolute value of data
Outputs data with a symbol as is.
Ao2 monitor bias adjustment
Biases data to adjust Point 0 of data.
Ao2 monitor gain adjustment
Cd-34 -1000.0 –
Apply a gain to data to adjust an inclination in
data.
Ao2 output level setting at Ao2
monitor adjust mode
Cd-35 -100.0 –
Sets output in the adjustment mode. It selects
the
-32]=00), or the
minimum output (at --32]=01).