INPUT POWER SUPPLY OVER-VOLTAGE PROTECTION
This function will output an error [E015] when the P-N voltage exceeds the voltage level set in the incoming overvoltage level
selection [bb-62] for 100 seconds continuously due to incoming voltage.
Power supply over-voltage error selection
bb-61
0 = warning
1 = error [E015]
Power supply over-voltage level
bb-62
600v – 820v (400v models)
300v – 410v (200v models)
OVER-TORQUE DETECTION
The over-function is used while operating in control modes (AA121) sensorless vector control (08), zero speed area
sensorless vector control (09), or
over-ror will occur [E053].
CE120
reverse regen
CE121
reverse
CE122
regen
CE123
TORQUE LIMIT
The function is used while operating in control modes (AA121) sensorless vector control (08), zero speed area sensorless
vector control (09), or vector control with encoder (10). This function can be used to protect the hoist and crane from damage
occurring due to snagging or over-loading
than this value.
under
Example – -68 = 2000 )
UE-68 2000 (default)