CLEARING FAULT HISTORY
To clear the fault history, use the step chart below.
Power on the VFD.
Press the #1 button one time to view the menu screen.
Use the arrow buttons to highlight “SCROLL MODE” and press the center dot button to enter the “SCROLL MENU”.
Use the arrow buttons to scroll down to “U:Set-up, PDN” and press the center dot to enter the “U parameter group”.
Press the #2 button once to change from the ‘UA’ group to the “Ub” group.
Use the arrow buttons to highlight parameter “Ub-01 Initialize Mode” and press the center dot to enter the “Ub-01”
parameter.
Use the arrow buttons to highlight the value “1 TRIP” and then press the #2 button to save the value. The screen will
automatically return to the “Ub” parameter listing.
Use the down arrow button to navigate and highlight parameter “Ub-05 Initialize” and press the center dot button to
enter the “Ub-05” parameter.
Use the arrow button to highlight “1 Initialize” and then press the #2 button to save the value. The VFD will clear the trip
history.
You can use the #1 button to return to the main screen by pressing it 3 times or just cycle power.