AUTO-TUNING
Field auto-configured from the factory for the connected motor. If field auto-tuning is
NOTE – The E-stop / maximum upper limit will retain function to prevent over-travel into the frame. The VFD will automatically control
the AL relay output for brake release command during auto-tuning.
IMPORTANT! – If a secondary brake is connected make sure the corresponding terminal function has been assigned to 62:LOG1
before starting the auto-tune.
Remove all attached loads from the hook. If you plan to do a rotational auto-tune remove the wire rope from the
drum.
Navigate to VFD parameter HA-01 and select 01: No Rotation for a static tune or 02: Rotation for a rotational tune.
Save the selection
On the VFD press the GREEN RUN button once and the auto-tune process will start. If there is an issue or you wish to
stop the auto-tune process, then press the RED STOP/RESET button.
Once the auto-tune process is complete the display with show the results of the R1,R2,L for a static tune or
R1,R2,L,IO,J for a rotational tune. The auto-tune data will automatically be applied to the motor constant parameters.
The auto-tune process is now complete.
MOTOR CONSTANTS
Hb102
Hb103 01: 4 pole motor
Hb106 230V / 460V
Hb108 14.0 A
Hb110 0.459108 ohms
Hb112 0.502048 ohms
Hb114 8.316144 mH
Hb116 6.11 A
Hb118 0.03176 kgm2