CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
126
BACnet PIC Statement The BACnet Feature
Supported - Binary Output
Present Value
BACnet
Enumeration
BACnet
LifeSafetyState
Fire Panel State
0 bpv_InActive Non-Fire Trouble, Non-Fire Device
Disabled, Normal
1 Bpv_Active Non-Fire Activation
Event State
BACnet
Enumeration
BACnet Event
State
Fire Panel State
0 EsNormal Normal
1 EsFault Non-Fire Trouble, Non-Fire Device
Disabled
2 EsOffNormal Non-Fire Activation
Reliability
BACnet
Enumeration
BACnet
Reliability
Fire Panel State
0 reNoFaultDet
ected
Non-Fire Activation, Non-Fire Device
Disabled, Normal
7 re_Unreliable
Other
Non-Fire Trouble
Status Flags
Boolean
BACnet Status
Flags
Fire Panel State
0,0,0,0 Normal Normal
1,0,0,0 InAlarm Non-Fire Activation
0,1,0,0 Fault Non-Fire Trouble
0,0,0,1 OutOfService Non-Fire Device Disabled
1,0,0,1 InAlarm,
OutOfService
If device is in Alarm state (Non-Fire
Activation) and also device goes to
disable state(Non-Fire Device
Disabled)
0,1,0,1 Fault,
OutOfService
If device is in trouble state (Non-Fire
Trouble)and also device goes to
disable state(Non-Fire Device
Disabled)
Out of Service
Boolean Fire Panel State
0 FALSE All statuses other than disable
1 TRUE Non-Fire Device Disabled