EasyManua.ls Logo

Honeywell CGW-MB - Page 128

Honeywell CGW-MB
187 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
127
BACnet PIC Statement The BACnet Feature
Supported - Binary Value Object
Present Value
BACnet
Enumeration
Fire Panel State
0 bpv_InActive Trouble, Device Disabled, Normal
1 Bpv_Active Activation
Event State
BACnet
Enumeration
BACnet Event
State
Fire Panel State
0 EsNormal Normal
1 EsFault Trouble, Device Disabled
2 EsOffNormal Activation
Reliability
BACnet
Enumeration
BACnet
Reliability
Fire Panel State
0 reNoFaultDet
ected
Activation, Device Disabled, Normal
7 re_Unreliable
Other
Trouble
Status Flags
Boolean
BACnet Status
Flags
Fire Panel State
0,0,0,0 Normal Normal
1,0,0,0 InAlarm Activation
0,1,0,0 Fault Trouble
0,0,0,1 OutOfService Device Disabled
1,0,0,1 InAlarm,
OutOfService
If device is in Alarm state (
Activation) and also device goes to
disable state(Device Disabled)
0,1,0,1 Fault,
OutOfService
If device is in trouble state
(Trouble)and also device goes to
disable state(Device Disabled)
Out of Service
Boolean Fire Panel State
0 FALSE All statuses other than disable
1 TRUE Device Disabled

Table of Contents