CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022 161
Gamewell-FCI Panels Connecting to the Panels
TB6 and RS-232 Connections
The pin connections are as below:
S3 Series Panel
At the TB3 terminal of the panel,
Connect the +ve wire to the TB3-1 pin.
Connect the -ve wire to the TB3-2 pin.
At the TB5 terminal of the panel,
Connect the GND wire to the TB5-1 pin.
Connect the TxD wire to the TB5-2 pin.
Connect the SUPV wire to the TB5-3 pin.
Connect the RxD wire to the TB5-4 pin.
Power Connection
On the CLSS Gateway mainboard Side
Ensure that the power cable is connected with the power port of the CLSS Gateway
mainboard.
The power port is labeled as 7 in the Figure C.15.
On the Panel Side
Connect the Red wire to the +ve pin in the TB2 port.
Connect the Black wire to the -ve pin in the TB2 port.