MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018 127
Appendix E: Default Programming
The following table provides a list of the programming options and their factory default settings.
Program Option Factory Default Program Option Factory Default
Zone #1-10 Enabled Yes ANN-80 Lock Enabled Yes
Zone #1-10 Type Pull Station ANN-80 Acknowledge Button Enabled Yes
Zone #1-10 PAS Pre-Signal Enabled No Delay ANN-80 Silence Button Enabled Yes
Zone #1-10 Verify Enabled No ANN-80 Reset Button Enabled Yes
Zone #1-10 ACC Message No Message Active ANN-80 Drill Button Enabled Yes
Zone #1-10 Freeze Enabled Yes ACC All-Call Zone None
Adjective None ANN-BUS Device 1 None
Noun None ANN-BUS Device 2 None
NAC #1-4 Enabled Yes ANN-BUS Device 3 None
NAC #1-4 Coding Steady ANN-BUS Device 4 None
NAC #1-4 Auto Silence No ANN-BUS Device 5 None
NAC #1-4 Silence Inhibit No ANN-BUS Device 6 None
NAC #1-4 Silenceable Silenceable ANN-BUS Device 7 None
Banner ANN-BUS Device 8 None
Relay 1 Alarm ANN-BUS Relay 1 type Zone 1
Relay 2 Trouble ANN-BUS Relay 2 type Zone 2
Relay 3 Supervisory ANN-BUS Relay 3 type Zone 3
Trouble Reminder No ANN-BUS Relay 4 type Zone 4
Canadian Option No ANN-BUS Relay 5 type Zone 5
Charger Disable No ANN-BUS Relay 6 type Zone 6
Factory Banner Factory Banner ANN-BUS Relay 7 type Zone 7
PAS Timer 120 ANN-BUS Relay 8 type Zone 8
Pre-Signal Timer 120 ANN-BUS Relay 9 type Zone 9
AC Loss Timer 2 ANN-BUS Relay 10 type Zone 10
Waterflow Delay Timer 0 Phone Line 2 Supervision Yes
Time Format 12 Hour Primary Phone Type Touchtone
Daylight Savings Enabled Yes Secondary Phone Type Touchtone
Daylight Savings Start Week Week 2 Central Station Reporting Enabled No
Daylight Savings Start Month March Central Station Report Type First Available
Daylight Savings End Week Week 1 Central Station Call Limit 0
Daylight Savings End Month November Central Station Primary Test Time Interval 24 Hr
Printer Port Type Parallel Port Central Station Primary Communication Format Ademco Contact ID
Printer Supervision No Central Station Primary Phone Number
Printer Baud Rate N/A Central Station Primary Test Time 1:00
Printer Parity N/A Central Station Primary Account Code 0000
Printer Data Bits N/A Central Station Secondary Test Time Interval 24 Hr
Printer Stop Bits N/A Central Station Secondary Communication Format Ademco Contact ID
Printer Offline Timer 60 Central Station Secondary Phone Number
ANN-BUS Enabled No Central Station Secondary Test Time 2:00
ANN-LED Piezo Enabled Yes Central Station Seocndary Account Code 0000
ANN-80 Piezo Enabled Yes Service Terminal Ring Count 0