MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018 99
Hazard/Tornado Condition Operation Operating Instructions
The alarm relay is not activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Note that, like supervisories, process monitor signals latch, except when programmed for process monitor autoresettable.
4.8 Hazard/Tornado Condition Operation
Hazard/Tornado operation is intended for Manual activation.
Hazard/Tornado Condition operation will initiate the following events:
The piezo sounder pulses ¼ second On, ¼ second Off
The LCD displays a hazard message along with the device name, type, adjective/noun, associated zones and time/date
Communicate the hazard condition to the Central Station (if the default event code has been changed from 000 to a reportable event
code)
Relays programmed for hazard will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Hazard conditions latch.
4.9 Medical Alert Condition Operation
Medical alert operation is:
not intended for nurse call stations (applications) per UL1069.
not intended for signaling professional medical staff.
to be used for summoning security guards or other trained personnel within the facility
intended for Manual activation.
Medical Alert Condition operation will initiate the following events:
The piezo sounder ¼ second On, ¼ second Off
The LCD displays a medical alert message along with the device name, type, adjective/noun, associated zones and time/date
Communicate the medical alert condition to the Central Station (if the default event code has been changed from 000 to a reportable
event code)
Relays programmed for medical alert will be activated
The alarm relay is not
activated
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Activate appropriate LED on the ANN-LED annunciator (required for this application)
Medical alert conditions latch.
4.10 Disable/Enable Operation
Input zones which are disabled do not cause an alarm or any zone activation. Disabled NACs are held in the off state. All disabled
zones/NACs are treated as if they were in trouble, with the exception being the status label that will be displayed is DISABL.
4.11 Waterflow Circuits Operation
If an alarm exists from a zone that is a waterflow non-silenceable type, the Alarm Silence key will not function.
4.12 Detector Functions
Maintenance Alert
i
3
smoke detectors will be polled for maintenance and freeze conditions on initial entry into Normal mode. Thereafter, each device will
be polled every hour for freeze and every four hours for maintenance conditions All alarm and system trouble conditions are annunci-
ated on the control panel’s LCD.
NOTE: To ensure that the system is functioning properly, the FACP will perform a freeze check five minutes after the panel is reset,
followed by a maintenance check. If there is no freeze or maintenance condition, the panel will continue to monitor for freeze conditions
every hour and maintenance conditions every four hours.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell FIRE-LITE MS-10UD Series and is the answer not in the manual?

Honeywell FIRE-LITE MS-10UD Series Specifications

General IconGeneral
BrandHoneywell
ModelFIRE-LITE MS-10UD Series
CategoryControl Panel
LanguageEnglish

Related product manuals