EasyManua.ls Logo

Honeywell FIRE-LITE MS-10UD Series - 3: ANN-SEC Option Card

Honeywell FIRE-LITE MS-10UD Series
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34 MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
Installation Installation of Optional Modules
Before installing the module, place the disconnect switch to the down (disconnect) position to prevent accidental activation of the munic-
ipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble LED will
turn on to indicate the Disconnect condition.
2.7.3 ANN-SEC Option Card
The ANN-SEC option card allows for a secondary ANN-BUS. Install the ANN-SEC as follows.
1. Remove the chassis mounting screw to the right of TB3 and replace it with the supplied 0.5” x 4-40 male-female standoff.
2. Install the header into J13 on the main circuit board.
3. Secure the ANN-SEC to the circuit board with the supplied screw.
Figure 2.17 4XTMF Transmitter Module
Connect to FACP Connectors J4 & J5
Disconnect
Switch
shown in
disconnect
position
TBL Jumper
}
Remote Alarm - Class 2
(power-limited)*
}
Remote Trouble - Class 2
(power-limited)*
No connection
1+
2-
3+
4-
5
6+
7-
Polarities are shown for module activation
Note: the 4XTMF Module is not directly suitable for transmitting reverse polarity supervisory signal.
For an application of reverse polarity of a supervisory signal, refer to the Appendix titled “FACP with
Keltron” on page 124.
* Wiring from these terminals
can exit the protected premises.
Dummy load terminals 6 and 7
(4.7KΩ, ¼ watt resistor) if
Municipal Box is not connected.
Disconnect LED
4xtmf.wmf
TB1
J1
ANN-SEC
FACP Circuit Board
connector to J13 on
main circuit board
standoff and screw
Figure 2.18 Installing the ANN-SEC Option Card
ann-secinst.wmf

Table of Contents

Related product manuals