16 MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
Product Description Specifications
The following figure illustrates the maximum current that is possible for each major panel output circuit and the total current available
from the FACP with the FLPS-7 power supply. This applies to the MS-5UD-7, MS-5UD-7C, MS-10UD-7, MS-10UD-7C, MS-5UD-7E,
and MS-10UD-7E.
TB9
TB5
TB7
TB3
TB1
Figure 1.2 Current Availability with FACP and FLPS-7 Power Supply
powerdistmrp.wmf
Refer to the battery calculations section for additional information.
Standby
1.0 amp max
per panel
Special Application
Nonresettable or
Resettable Power
Special Application
Resettable Power
NAC #1
NAC #2
NAC #3
NAC #4
0.5 amp max
per circuit
0.5 amp max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
3.0 amps max
per circuit
Alarm
7.0 amps max
per panel
Primary
ANN-BUS
Standby
1.0 amp max
per panel
0.5 amp max
per circuit
0.5 amp max
per circuit
ANN-SEC
Option Card

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell FIRE-LITE MS-10UD Series and is the answer not in the manual?

Honeywell FIRE-LITE MS-10UD Series Specifications

General IconGeneral
BrandHoneywell
ModelFIRE-LITE MS-10UD Series
CategoryControl Panel
LanguageEnglish

Related product manuals