MOUNTING
Duct Mounting
Before beginning Duct Mounting:
Ihaveconrmedlocalcodesforproperdrainingpracticesforhotwater
I have chosen an installation location that meets the requirements on page 4
FollowthesestepstomountTrueSTEAMdirectlytothesupplyductofthehomeowner’sHVACequipment.
STEP ONE: Select a Mounting Location
Choosealocationthathasaccesstoacold
watersupplypipe.
SelectaverticalorhorizontalsurfaceontheHVAC
supplyduct,withadequateclearances,where
TrueSTEAMcanbemounted.
Makesurethereisa120VACelectricaloutlet
ratedfortheTrueSTEAMmodelbeinginstalled.
Ensurethelocationisnearadrainwithahigh-
temperaturewaterrating.Consultlocalplumbing
codesforproperdrainage.Ifnomainoordrain
is available, see “Appendix E: Advanced Draining”
on page 41.
STEP TWO: Connect the Duct Nozzle
Slidethefoamgasketoverthenozzle.
Makesuretheo-ringgasketisproperlyseated
inthegroove.
InserttheductnozzleintoTrueSTEAM.Twist
clockwisetoensureatightseal.
M29598
M29599
TrueSTEAMHumidicationSystem69-2285EF—01
6
TrueSTEAM Required Minimum
Model: Circuit Capacity:
HM506 7Amps
HM509 10Amps
HM512 12Amps
1
4
2
3
3
2
1