Code Error Causes
Measures
Restart mode after the
measure.
Operation
Status
LED
Status
Diagnostic
Timing
still exists after turning it
on again.
turning it
on.
13 Abnormal base
information
Contact A/S service if it
still exists after turning it
on again.
STOP ERR : On When
turning it on
converting
to RUN
mode.
22 The program of
backup flash is
defective
Restart after modifying
the program of the
backup flash.
Fault ERR : On Reset
converting
to RUN
mode.
23 If a program to
execute is not
normal
Operate after the
program is
reloaded.Replace a
battery in case of
abnormal battery.
After a program is
reloaded, check the
storage condition and if
any fault is found,
replace the CPU
module.
STOP ERR : On Reset
converting
to RUN
mode.
24 Abnormal I/O
parameter
Restart after I/O
parameter is reloaded.
Replace a battery in
case of defective battery.
After I/O, parameter is
reloaded, check the
storage condition, and if
any fault is found,
replace the CPU
module.
STOP ERR : On Reset
converting
to RUN
mode.
25 Abnormal basic
parameter
Restart after basic
parameter is
reloaded.Replace a
battery in case of
defective battery.
After basic parameter is
STOP ERR : On Reset
Converting
to RUN
mode.
- 56 -
Chapter 4 - Troubleshooting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ML200 Series and is the answer not in the manual?

Honeywell ML200 Series Specifications

General IconGeneral
BrandHoneywell
ModelML200 Series
CategoryController
LanguageEnglish

Related product manuals