Chapter 4 - Troubleshooting
Code Error Causes
Measures
Restart mode after the
measure.
Operation
Status
LED
Status
Diagnostic
Timing
reloaded, check the
storage condition and if
any fault is found,
replace the CPU
module.
30 The module set in
parameter and
the actually
installed module
do not coincide
Check the wrong slot
position by SoftMaster,
modify a module or
parameter, and then,
restart.
Reference flag: module
type inconsistence error
flag.
STOP
(RUN)
ERR : On
(P.S. :
On)
Converting
to RUN
mode.
31 Module
detachment or
module addition
during operation
Check for
detached/added slot
position by SoftMaster,
modify the installment,
and restart (according to
parameter).
Reference flag: module
attachment error flag.
STOP
(RUN)
ERR : On
(P.S. :
On)
When the
scan ends.
32 Fuse of a module
holding a fuse is
burnt out during
operation
Check the position of a
slot of which fuse is burnt
out by SoftMaster,
replace a fuse and
restart (according to
parameter).
Reference flag: fuse
disconnection error flag.
STOP
(RUN)
ERR : On
(P.S. :
On)
When the
scan ends.
33 IO module data
cannot be
successfully
accessed during
operation
Check the position of a
slot with access error by
SoftMaster, replace the
module and restart
(according to
parameter).
Reference flag: I/O
Module Write/Read
error flag.
STOP
(RUN)
ERR : On
(P.S. :
On)
When the
scan ends.
- 57 -

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell ML200 Series and is the answer not in the manual?

Honeywell ML200 Series Specifications

General IconGeneral
BrandHoneywell
ModelML200 Series
CategoryController
LanguageEnglish

Related product manuals