EasyManua.ls Logo

Honeywell MPA2 - Communications; USB Communications Setup

Honeywell MPA2
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing the MPA2 Panels
Installation
MPA2 Access Control Unit Installation Guide, Document 800-25395 - B 39
Table 9 Downstream I/O Devices DIP Switch and Jumper Settings
Note: If a NX4IN is not required in a system, start addressing the NX4OUT at
DIP switch 3. If a NX4IN is configured with an address other than 1 or 2, the
MPA2 panel will not communicate with it. Likewise, if a NX4OUT is
configured with an address other than 3 through 6, the MPA2 panel will not
communicate with it.
The MPA2 board is not intended to provide either module power or module
output load power for downstream I/O. A separate 24 VDC supply should
be used to provide power to all downstream modules and output loads.
Module Setting Value
NX4IN DIP switches Address (switches 1-6) - 1 or 2
Baud rate (switches 7 and 8) - 7 = OFF, 8 = ON
OP Mode (switches 9 and 10) - 9 = OFF, 10 = OFF
Jumper settings JP1 – ON, positions 1 and 2 (if the module is the
last module on the downstream bus),
OFF positions 2 and 3 (if the module is not the last
module on the downstream bus)
JP2 - any setting
JP3 - any setting
JP4 - NORMAL
(Positions 1 and 2)
NX4OUT DIP switches Address (switches 1-6) - 3 through 6
Baud rate (switches 7 and 8) - 7 = OFF, 8 = ON
OP Mode (switches 9 and 10) - 9 = OFF, 10 = OFF
Jumper settings JP1 - ON, positions 1and 2 (if the module is the last
module on the downstream bus);
OFF, positions 2 and 3 (if the module is not the last
module on the downstream bus)
JP2 - NORMAL, positions 1
and 2

Table of Contents

Other manuals for Honeywell MPA2

Related product manuals