Revision 1.0 SMV800 Modbus User's Guide Page 151
Bore Material
292
Shows currently selected
Bore Material. This is user
configurable parameter.
Available Bore Material is
dependent upon the Flow
Calculation Standard and
Algorithm Options. Note that
only Advanced
Algorithms Options Supports
GOST material/Standard.
R/W
uint8
When Flow Calc Standard
is other than GOST :
0 = 304 Stainless Steel
1 = 316 Stainless Steel
2 = 304/316 Stainless
Steel
3 = Corbon Steel
4 = Hastelloy
5 = Monel 400
6 = Other
When Flow Calc Standard
is GOST:
0 = 35Π
1 = 45Π
2 = 20XMΠ
3 = 12X18H9TΠ
4 = 15K,20K
5 = 22K
6 = 16ГC
7 = 09Г2C
8 = 10
9 = 15
10 = 20
11 = 30,35
12 = 40,45
13 = 10Г2
14 = 38XA
15 = 40X
16 = 15XM
17 = 30XM,30XMA
18 = 12X1MФ
19 = 25X1MФ
20 = 25X2MФ
21 = 15X5M
22 = 18X2H4MA
23 = 38XH3MФA
24 = 08X13
25 = 12X13
26 = 30X13
PV Simulation
Fail Safe
293
Configures Temperature and
Static Pressure failsafe
ON/Off conditions, Reverse
Flow ON/OFF condition and
Simulation ON / OFF
conditions for Process
Variables DP, SP, PT, Flow
R/W
uint8
Bit 0 :-> 0 = Off, 1 = pv2
failsafe
Bit 1 :-> 0 = Off, 1 = pv3
failsafe
Bit 2 :-> 0 = Off, 1 =
reverse flow on
Bit 3 :-> 0 = Off, 1 =
simulate DP
Bit 4 :-> 0 = Off, 1 =
simulate SP
Bit 5 :-> 0 = Off, 1 =
simulate PT
Bit 6 :-> 0 = Off, 1 =
simulate Flow
Bit 7 :-> reserved
Simulated DP
294
Simulated DP value when
Simulation setting is ON
RO
float
N/A
Simulated SP
296
Simulated SP value when
Simulation setting is ON
RO
float
N/A
Simulated PT
298
Simulated PT value when
Simulation setting is ON
RO
float
N/A