Revision 1.0 SMV800 Modbus User's Guide Page 159
Display SW
Rev
507
Advanced Dissplay Software
Revision
RO
uint8
N/A
Display Type
511
Identifies the type of Display
connected to the device
(only Advanced Display is
available for SMV Modbus
devices)
RO
uint8
0 = No Display Connected
1 = Advanced Display
connected
Screen
Number
512
Display screens from 1 to 8
R/W
uint8
N/A
Screen Format
513
View display format:
R/W
uint8
0 = None
1 = PV
2 = BAR Graph
3 = Horizontal Trend
PV Selection
514
process variable
R/W
uint8
0 = PV Unused
1 = Diff. Pressure
2 = Absolute Press
3 = Temperature
4 = Mass Flow
5 = MB Temperature
6 = Sensor 1 Resis
7 = Totalizer
8 = User Variable1
9 = User Variable2
10 = User Variable3
11 = User Variable4
12 = User Variable5
13 = User Variable6
14 = User Variable7
15 = User Variable8
Display Unit
515
Engineering units code.
R/W
uint8
Decimals
516
Number of digits to display
after the decimal point
R/W
uint8
0 = x
1 = x.x
2 = x.xx
3 = x.xxx
PV Scaling
517
When Convert Units is
selected, the selected PV
Selection parameter will
show the values in converted
Engineering Unit.
Else the values will be
shown in default Engineering
Unit
None, Convert Units, Linear
Not Applicable to Sensor
Resis.
None, Linear, Convert Units
applicable to Diff Press,
Gauge/Absolute Press,
Temp, Meter Body Temp,
Mass/Volume
Flow, Sensor, Totalizer
R/W
uint8
0 = None
1 = Convert EU
2 = Linear
Trend
Duration
518
Duration of the trend screen
in hours.
R/W
uint8
N/A