Page 160 SMV800 Modbus User's Guide Revision 1.0
Scaling Units
519
The text configured to be
displayed for custom
units
R/W
uint8
N/A
Screen
Custom Tag
528
Character string to identify
the displayed value (14
characters + null) -
sized to support Unicode
characters
R/W
ASC
CII
N/A
Reserve For
Device
Specific
543
Incremented each time a
value in this table is
changed.
R/W
uint8
N/A
Scaling High
544
The value configured as the
Scaling High Limit for
PV Scaling selections of
linear.
R/W
float
N/A
Scaling Low
546
The value configured as the
Scaling Low Limit for
PV Scaling selections of
linear.
R/W
float
N/A
Disp Low Limit
548
Display Low Limit (Trend,
Bar Graph - usually equal to
LRV)
R/W
float
N/A
Disp Hi Limit
550
Display High Limit (Trend,
Bar Graph - usually equal to
URV)
R/W
float
N/A
Display
Connected
552
Identifies whether a Display
is connected to the
device.
RO
uint8
0 = Not connected
1 = connected
Language
Package
553
shows type of language
package loaded in advanced
display.
RO
uint8
0 = None
1 = Western Language
Pack
2 = Easter Language Pack
User Variable 1
601
User defined varaible 1
R/W
float
N/A
User Variable 2
603
User defined varaible 2
R/W
float
N/A
User Variable 3
605
User defined varaible 3
R/W
float
N/A
User Variable 4
607
User defined varaible 4
R/W
float
N/A
User Variable 5
609
User defined varaible 5
R/W
float
N/A
User Variable 6
611
User defined varaible 6
R/W
float
N/A
User Variable 7
613
User defined varaible 7
R/W
float
N/A
User Variable 8
615
User defined varaible 8
R/W
float
N/A
User
Var1_LRV
617
User defined variable 1 lower
range value.
R/W
float
N/A
User
Var1_URV
619
User defined variable 1
upper range value.
R/W
float
N/A
User
Var2_LRV
621
User defined variable 2 lower
range value.
R/W
float
N/A
User
Var2_URV
623
User defined variable 2
upper range value.
R/W
float
N/A
User
Var3_LRV
625
User defined variable 3 lower
range value.
R/W
float
N/A
User
Var3_URV
627
User defined variable 3
upper range value.
R/W
float
N/A