Revision 1.0 SMV800 Modbus User's Guide Page 163
Communicaito
n Module ET
Max. limit
719
Communications board
Electronics Temperature
(ET) highest
operating limit from
specification.
RO
Float
Communicaito
n Module ET
Min. Value
721
Communications board
Electronics Temperature
(ET) lowest measured value
RO
Float
Communicaito
n Module ET
Max. Value
723
Communications board
Electronics Temperature
(ET) highest
measured value
RO
Float
Communicaito
n Module ET
Value
725
Communications board
Electronics Temperature
(ET) highest
measured value
RO
Float
Maximum
Totalizer
Value.
745
This is a user configurable
value indicating the
maximum Totalizer value.
When the Totalizer Value
reaches this maximum value,
it automatically resets to zero
and continues totalizing. It
also increments the Exceed
Counter. On a Negative
Totalizer Max value, with a
decreasing Total Flow value,
Totalizer will reset only on
crossing the negative max
value. Ex: Totalizer Max = -
1000lb
On an emptying Tank, say
Totalizer reaches -100, -200,
-300 etc. Even though -100, -
200 etc are greaterthan -
1000, this does not cause
Totalizer Reset until after the
Totalizer goes below -1000.
Here Exceed counter will be
incremented every time
Totalizer reaches below -
1000 lb.
R/W
float
N/A
Totalizer
Value
747
This is the Totalized Flow as
calculated based on the flow
rate during the time that the
Totalizer is in Run mode.
The Totalizer will
increment during Forward
(positive) flow and
decrement during Reverse
(negative) flow. Note: the
Reverse Flow configuration
setting must be enabled to
calculate negative flow.
RO
float
N/A