Page 62 SMV800 Modbus User's Guide Revision 1.0
This is the Totalizer sampling rate. The
Totalizer value will be updated at the
configured rate. The rate may be configured
in increments of 125 ms. The shorter the
sampling rate, the more frequently the
Totalizer Value will be updated.
When the Totalizer is set to Run mode after
a Reset, it will start
incrementing/decrementing from this base
value.
This value indicates the number of times the
Totalizer Value has reached the user-
configured Maximum Totalizer Value.
Each time the Totalizer Value has reached
the Maximum Totalizer Value, the Max
Totalizer Status will be set. The user-
configurable Totalizer Status Latency
indicates the length of time this status will
be active before it is reset.
This parameter indicates the current status
of the Totalizer Value. Possible values are:
- Good
- Bad
- Totalizer OFF
- Simulation Mode Active
Start/Stop
Reset Positive Totalizer
Reset Negative
Totalizer
Reset Totalizer Exceed
Counter
This method will allow the user to:
Start or stop the totalizer
Reset the Positive Totalizer to zero
or to the configured Totalizer base
Value
Reset the Negative Totalizer to zero
or to the configured Totalizer base
Value
Reset the Totalizer Exceed Counter
to zero
Note: Based on the host implementations, user entered values for Totalizer ranges and
limits will be rounded off to 7 digits (this includes the digits before and after the decimal
point) and rest will be filled with 0’s (digits 8 and above) to represent the values in IEEE
floating point format.
This will be the value that gets written to the device.
For example:
4567.12459 will be rounded to 4567.125
12345678 will be rounded to 12345680
123456789 will be rounded off to 123456800