Technical specifications 19
TECHNICAL SPECIFICATIONS
Communication Technologies
Electrical Characteristics
Supported Sensors and Functions
Table 7: Communication Technologies
Sylk
TM
Honeywell Sylk
TM
BACnet MS/TP Over RS485
(9.6, 19.2, 38.4, 76.8, 115.2 Kbps)
Modbus RTU 1.2 to 115.2 Kbps
Table 8: Electrical Characteristics
Rated Impulse Voltage 500 V
Construction of Control Independently Mounted Control
Operation Method Type 1.B Action
Pollution Degree 2
Purpose of Control Operating Control
Table 9: Supported Sensors
Sensors Options Part Numbers
Occupancy Sensor Direct
(Normally Open)
Reverse (Normally Closed)
Dry contact occupancy sensor
Proof Of Air Flow Sensor Direct
(Normally Open)
Reverse (Normally Closed)
DPS200
DPS400
DPS1000
MCS, CS, CSP current switches
(Dry contact switches)
Discharge Air
Temperature Sensor
NTC 20K
NTC 10K Type II
NTC 10K Type III
Sylk
C7250A
C7041
C7021
C7023
C7400S
Space Temperature
Sensors
NTC 20K
NTC 10K Type II
NTC 10K Type III
Sylk
TR21
C7041, C7772A, C7021, C7772F,
C7023, C7772G,
TR40,
TR40-H,
TR40-CO2,
TR40-H-CO2,
TR50-3N, TR50-3D

Table of Contents