EasyManuals Logo

Honeywell TC300 User Manual

Honeywell TC300
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
76 Managing Valve purge
4 - CONFIGURATION
Managing Valve purge
This setting for 2-pipe systems cycles valve to ensure accurate changeover
temperature sensor reading if there are infrequent heating or cooling cycles.
To configure Valve purge
1. Swipe left from the Home screen.
2. On the Quick access screen, tap > Advanced > Valve Purge.
The Valve Purge screen appears.
Figure 55 Valve purge
3. Set the purge time and interval.
Hybrid
Control
Temp Offset (Heat) 5 to 10°F (Default
5°F)
When the pipe temperature is above the
space temperature and the hybrid control is
enabled, than the offset is suitable for
heating.
Timeout Timer
(Heat)
1 to 4 hours (Default 4
hours)
When the configured timer expires, the pipe
sensor reading is compared to the threshold
setting, if the pipe sensor reading is above
the threshold, it will generate water
temperature. No heating alarm will be
raised.
Temp Offset (Cool) -10 to -5°F (Default
-5°F)
When the pipe temperature is below the
space temperature and the hybrid control is
enabled, than the offset is suitable for
cooling.
Timeout Timer
(Cool)
1 to 4 hours (Default 4
hours)
When the configured timer expires, the pipe
sensor reading is compared to the threshold
setting, if the pipe sensor reading is below
the threshold, it will generate water
temperature. No cooling alarm will be raised.
Table 26: Pipe sensor threshold (Continued)
Operation Configuration
Type
Range Description

Table of Contents

Other manuals for Honeywell TC300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell TC300 and is the answer not in the manual?

Honeywell TC300 Specifications

General IconGeneral
BrandHoneywell
ModelTC300
CategoryThermostat
LanguageEnglish

Related product manuals